GW13-126kV Disconnect switch-GW13-126kV Disconnect switch-Disconnect Switch -Product-BAODING JIKAI POWER EQUIPMENT CO., LTD.

BAODING JIKAI POWER EQUIPMENT CO., LTD.

  • Products
  • Service
  • Solution
  • GW13-126kV Disconnect switch

    GW13-126kV Disconnect switch

    Views:

    Product Overview:

        GW13 series improving type disconnect switch is double column horizontal fracture 50HZ three phase alternating current outdoor high-voltage equipment,for high-voltage lines interchang at load-free.

    Main Feature:


    1.Contact finger is made of the new material which with high-strength,high conductivity and high flexibility,Rely on itself elastic force to clamp the contactor,so it avoids the vicious circle which caused by the corrosion of the spring,annealing and febrile,such as the clamping force to reduce,the contact resistance to increase and the cantactor radiation.
    2.Using the fixed soft connection flow between the connector base and connection terminal,and in the both ends of the terminals.
    Using insulating sleeve ,to ensure that the flow of reliable,flexible rotation.
    3.All-sealed bearing,the bearing surface to meet the amount of molybdenum disulfide lithium base grease to emsure a reliable long-term rotation.
    4.Using 180 degree operation mechanism make sure the reliability while the switch blade are at the breaking-closing position as the active crankarms of the breaking-closing are at the dead center position.


    Main Technical Parameter:

     

    Product model
    Rated
    voltage
    (kV)
    Rated
    current
    (A)
    Thermal stability current
    (effective value)
    (kA)
    Moving stability current
    (peak value)
    (kA)
    1min frequency voltage
    (effective
    Value)
    kV
    Lightning impulse withstand voltage
    (peak value)
    (kV)
    Terminal horizontal pul
    (N)
    Monopolar
    weight
    (kg)
    Over the ground
    Between contancts
    Over the ground
    Between contancts
    GW13-72.5/630
    72.5
    630
    25
    50
    155
    325
    325
    375
    750
    120
    GW13-126/630
    126
    1250
    25
    50
    230
    265
    550
    630
    750
    150

    Outline and Install Size

    GW1-12/630A Outline size of disconnect switch
    Remart:There is the outline size of 126kV model in the brachek